Software Analysis - ASPIRES

Software Analysis - ASPIRES

LabelSourcePropertySub-property ofRangeUsageVocab SchemaSyntax SchemaObligation

Example 1: Fault

(E#DT_1117_2151_00)

Example 2: Capacitor   
Common fields             
Relative locationASPIRES   Relative location of the event with respect to the PQ monitordownstream, upstream 0-1downstream    
Duration (Phase A & B & C)ASPIRES  json objectDuration of the disturbance (cycles)  0-1

{'C': 2.37}

    
Real power variation (Phase A & B & C)ASPIRES  json objectReal power variation after the event (kW)  0-1

{'A': -4.68,

'B': 2.83,

'C': -102.01}

    
Reactive power variation (Phase A & B & C)ASPIRES  json objectReactive power variation after the event (kvar)  0-1

{'A': -0.60,

'B': 0.52,

'C': -40.6}

    
Peak instantaneous current (Phase A & B & C)ASPIRES  json objectPeak current magnitude (kA)  0-1

{'A': 0.070,

'B': 0.400,

'C': 0.996}

    
              
Fault events only             
RMS current disturbance duration (Phase A & B & C)ASPIRES  json objectDuration of the current rms disturbance (over-current) (cycles)  0-1

{'C': 2.75}

    
RMS voltage magnitude variation during fault (Phase A & B & C)ASPIRES  json object

RMS voltage variation during the fault and before the fault (%)

  0-1

{'A': 5.76,

'B': -1.38,

'C': -26.58}

    
RMS voltage disturbance duration (Phase A & B & C)ASPIRES  json objectDuration of the voltage rms disturbance (sag or swell) (cycles)  0-1

{'C': 2.25}

    
Estimated fault location (simple reactance, Takagi)ASPIRES  json object

Estimated fault locations (simple reactance method, Takagi method) (miles)

  0-1

{'SR': 10.46,

'Takagi': 11.07}

    
Estimated fault clearing deviceASPIRES   Estimated fault clearing device  0-1recloser    
Fault typeASPIRES   Phase(s) involved in the short-circuit faultAG, BG, CG, AB, ABG, BC, BCG, CA, CAG, ABC, ABCG 0-1CG    
Pre-fault phasor angle (Phase A & B & C & 0 & -)ASPIRES  json objectCurrent phasor angle with respect to voltage phasor, before fault (deg)  0-1

{'A': -11.35,

'B': -15.03,

'C': -12.89,

'0': 90.66,

'-': 106.74}

    
During-fault angle (Phasor A & B & C & 0 & -)ASPIRES  json objectCurrent phasor angle with respect to voltage phasor, during fault (deg)  0-1

{'A': -25.40,

'B': -19.55,

'C': -45.05,

'0': 92.34,

'-': -51.67}

    
              
Capacitor switching events only             
Peak instantaneous voltage (Phase A & B & C)ASPIRES  json objectAbsolute peak voltage magnitude during the disturbance (kV)   

 

    
Steady state RMS voltage variation (Phase A & B &C)ASPIRES  json object

Steady state RMS voltage variation before and after the disturbance (%)

   

 

    
Switching angle (Phase A & B & C )ASPIRES  json object

Voltage phase angle at the capacitor switching instant (degrees). The reference (0 degree) is the most recent positive-going zero crossing before the disturbance.

   

 

    
Resonant frequency (Phase A & B & C)ASPIRES  json objectResonant frequency of the transient disturbance (Hz)   

 

    
Power factor variation (Phase A & B & C)ASPIRES  json objectPower factor variation before and after the disturbance   

 

    
THD - voltage (A & B & C)ASPIRES  json objectTHD voltage variation before and after the disturbance (%)   

 

    
              
              
IEEE disturbance classificationASPIRES    IEEE DisturbanceCategory of this event according to the IEEE standard 1159-2009  0-n