First pass by SRB, updated EMK 5/4/2011 As Sublimator detail added by SDS 5/20/2015Temperatures:
Al: Before melting 1.7% manual power, After melting 800C (with backup UPS in-line)
AsCrk: 850C
AsSub: 320C
InTip: 350C
InBase: currently OFF
GaTip: 350C
GaBase: currently OFF
La: 1000 C
Gd: 600 C
Lu: 700 C
BiTip: 310 C
BiBase: 300 C
Si: 350C
Be: 350C
Substrate: 200C or 4.5%
HTS: 10C or 0%
LCLamp: 10C or 0%
Heated Viewport 400C
CAR:
Beam Flux gauge on
In Transfer Position
As Sublimator:
When not growing with As, set the As Eurotherm in Auto mode at 357C. This is approximately 29.5% power. This setting may change depending on the needs of the various growers.
During growth, put the As Sub Eurotherm in Manual mode.
Standard Manual mode setting is 29.5%. This may change depending on requirements of the various growers.
PID values for Eurotherms (Pt, Ti, Td):
LC Lamp: 106, 38, 6